8.9.3A weighted sample of 175 to 225 grams of liquid CFC-12 is allowed to evaporate at room temperature. 1)Type of freon 3.2The equipment must be certified that it meets this specification by Underwriters Laboratories Inc. (UL), or by an equivalent Nationally Recognized Testing Laboratory (NRTL). 4.1Moisture and AcidThe equipment shall incorporate a desiccant package that must be replaced before saturated with moisture and whose mineral acid capacity is at least 5% by weight of total system dry desiccant. The assembly of the parts shall, as an outside-the-vehicle package, duplicate the OE system and its routing, including bends, except for permitted additions of bends and/or loops in refrigerant lines. The vehicle system's service valve cores must remain in the fittings for this procedure. 6.3Portable refillable containers used in conjunction with this equipment must meet applicable DOT standards. Type 1 cert. 6.7The equipment must be able to separate the lubricant from recovered refrigerant and accurately indicate the amount removed from the simulated automotive system during processing in 20 mL (0.7 fl oz) units. -hydropfluoric acid May not be returned to a motor vehicle air conditioning system without first being recyceled or reclaimed. system water pump length of hoses 8.9.1The amount of noncondensable gases shall be determined by gas chromatography. Use these flashcards to help memorize information. as what? The scale must maintain accuracy when moved, as per the test in Section 10. The marking shall indicate that retest must be performed every subsequent 5 years. (f) Refrigerant means any class I or class II substance used in a motor vehicle air conditioner. If an alternative method of measuring refrigerant is used, follow the equipment manufacturer's procedure for ensuring accuracy. The purpose of this standard is to provide equipment specifications for the recovery of any refrigerant other than CFC-12 or HFC-134a for return to a refrigerant reclamation facility that will process it to ARI Standard 700-93 (or for recycling in other EPA approved recycling equipment, in the event that EPA in the future designates a standard for equipment capable of recycling refrigerants other than CFC-12 or HFC-134a). unit condens. Should you run the compressor in a system when pulling a vaccum? c. Weigh the tank, on a scale accurate to plus/minus 3 grams. The refrigerant in this document shall have been directly removed from, and intended to be returned to, a mobile air-conditioning system. 7.3Start the timer. Sec. To prevent system delayed outgassing, the unit must have a device that assures that the refrigerant has been recovered from the air-conditioning system. This procedure provides service guidelines for technicians when repairing vehicles and operating equipment defined in SAE J1990. (3) Notwithstanding any other terms of this paragraph (e), approved refrigerant recycling equipment may be transported off-site and used to perform service involving refrigerant at other locations where such servicing occurs. 6.3.3During operation, the equipment shall provide overfill protection to assure that the storage container liquid fill does not exceed 80% of the tank's rated volume at 21 C per DOT Standard, 49 CFR 173.304, and the American Society of Mechanical Engineers. See our This test procedure and its requirements are to be used to determine the ability of the recycling equipment to adequately recycle contaminated refrigerant. 9.1.2The equipment shall clean the contaminated CFC-12 refrigerant to the minimum purity level as defined in Appendix A, when tested in accordance with the requirements in section 8.1. when evac. -hydrochloric acid A Propak Q column at 130 C and a hot wire detector may be used for analysis. The manufacturer must document changes made to improve accuracy and furnish them to the laboratory prior to a new test. LEFT ARROW - move card to the Don't know pile. How does a self-contained recover system work? 5.2The equipment must prominently display the manufacturer's name, address, the type of refrigerant (CFC-12 and HFC-134a), a service telephone number, and the part number for the replacement filter/drier. 7.1.3The refrigerant that is recovered, following oil separation, shall be measured and the quantity displayed, accurate to within 30 g (1.0 oz). What is the job of the drier in a ac system? When recovery is completed, including from service hoses if that is part of the recommended procedure, disconnect hoses and drape over machine. (change from 12 to 22), moisture absorption. manuf. -be hydrostatically tested 4.2The equipment must comply with applicable safety standards for the electrical and mechanical systems. The following publications form a part of the specification to the extent specified herein. After charging a system using manifold gauages, refrigerant in the hoses After initial recovery procedures, the technician should wait 5 minutes to determine if the system returns to a positive pressure. 5.1.1The instruction manual shall include the following information on the lubricant removed. (f) Authorized representatives of the Administrator may require technicians to demonstrate on the business entity's premises their ability to perform proper procedures for recovering and/or recycling refrigerant. Recovery Cylinders must have what sort of certification? Captures refrig. 3.3The equipment must be certified by Underwriters Laboratories or an equivalent certifying laboratory. The marking shall be in letters at least 6 mm high. Use only new lubricant to replace the amount removed during the recycling process. 3.4The equipment shall have a label Design Certified by (Company Name) to Meet SAE J1991. Should you run the compressor in a system when pulling a vaccum? 6.3.2Portable refillable containers used in conjunction with this equipment must meet applicable DOT Standards. $$ -moisture -refrigerant oil -and non-condesable gases to the levels set by the Society of Automotive Engineers. 2.1Applicable DocumentsThe following publications form a part of this specification to the extent specified. How does a System-dependant recovery device work? Records required under this paragraph must be retained for a period of three years. Clean air act mandates all people servicing motor vehicle AC must, -use EPA approved Equip. This definition does not include a vehicle where final assembly of the vehicle has not been completed by the original equipment manufacturer. Prior to recharging a system with recycled refrigerant, the refrigerant should be checked for? 6.7The equipment must be able to separate the lubricant from the recovered refrigerant and accurately indicate the amount removed from the system during processing in 30 ml units. The only permitted engine operation is as specified in 7.1. 8.5.1Samples of the standard contaminated refrigerant from 8.3.1 shall be processed as required in 8.6 and shall be analyzed after said processing as defined in 8.7, 8.8, and 8.9. after the date? The manufacturer must document changes made to the machine to improve its performance before a new test is allowed, and furnish them to the laboratory. 6.3.1Contaminated HFC-134a (R-134a) sample shall be standard contaminated HFC-134a (R-134a) refrigerant, 13.6 kg sample size, consisting of liquid HFC-134a (R-134a) with 1300 ppm (by weight) moisture at 21 C (70 F) and 45 000 ppm (by weight) of oil (polyalkylene glycol oil with 46-160 cst viscosity at 40 C) and 1000 ppm by weight of noncondensable gases (air). size of pump Test vehicle shall be overnight cold (not run for at least eight hours). The marking shall be in letters at least 6 mm high. In any event, approved equipment must be used to extract refrigerant prior to performing any service during which discharge of refrigerant from the motor vehicle air conditioner can reasonably be expected. 5.1The equipment manufacturer must provide operating instructions that include information equivalent to that required by SAE J1629, necessary maintenance procedures, and source information for replacement parts and repair. of refrig manuf. 5.4Compare the observed container pressure and air temperature to determine if the container exceeds the pressure limits found on Table 1, e.g., air temperature 70 F (21 C) pressure must not exceed 80 psig (5.62 kg/cm2). ac system LOW press GAS is found b/t what? Systems used on mobile vehicles for refrigerated cargo that have hermetically sealed systems are not covered in this document. 10.2.1The recycled liquid phase sample of refrigerant shall be analyzed for moisture content via Karl Fischer coulometer titration or an equivalent method. 7.1The equipment must be capable of ensuring recovery of the R-12 from the system being service, by reducing the system pressure below atmospheric to a minimum of 102 mm of mercury. 2. Operation manuals must cover information for complete maintenance of the equipment to assure proper operation. when charging a low press. 4.1The equipment must comply with applicable federal, state, and local requirements on equipment related to the handling of the applicable refrigerant material. How much can be a paid to a person supplying information that leads to a penalty against a technician who is intentionally venting? If a blend contains HCFC-22 all hoses must be replaced with what type of hoses? hcfc 22 app. b. Programs are encouraged to make provisions for non-English speaking technicians by providing tests in other languages or allowing the use of a translator when taking the test. ), so the technician has an accurate basis for adding oil to the system. (2) Equipment manufacturers or owners may request a determination by the Administrator by submitting an application and supporting documents that indicate that the equipment is substantially identical to approved equipment to: MVACs Recycling Program Manager, Stratospheric Protection Division (6205J), U.S. Environmental Protection Agency, 1200 Pennsylvania Ave., NW., Washington, DC 20460, Attn: Substantially Identical Equipment Review. process what has most likely occured? 1.13 kg (2.56 lb) samples are to be processed at 5 min intervals. (J) Owners or lessees of recycling or recovery equipment having their places of business in Alaska, Idaho, Oregon, Washington must send their certifications to: CAA section 609 Enforcement Contact; EPA Region X (OAQ-107); 1200 Sixth Avenue; Seattle, WA 98101. The tank must hold that vacuum with a decay of less than 10% in 10 minutes. -never intentially vent refrigerant (oops! To remove non-condesable gases A recovery cylinder must be emptied to what prior to transferring recycled refrigerant into an empty storage cyclinder? process refrigerant to a level equal to new product specs as determined by chemical analysis. 7.6.2The equipment must be provided with some means, such as a lockout device, which will prevent initiation of the recovery operation after switching to the other refrigerant, if the lubricant has not been drained from the oil separator. The elapsed time shall be no more than 30 minutes. 8.2.3Following the preconditioning procedure per section 8.2.2, 18.2 kg of standard contaminated HFC-134a are to be processed by the equipment at each stable ambient temperature of 10, 21, and 49 C. -refrigerant oil A scale to measure the potential of chemical for destroying ozone. Equipment that fails to meet appropriate standards will not be considered approved. 3 things required for refillable cylinders, -be UL or DOT approved The fixture system shall be powered by an electric motor, run at a speed not to exceed 2000 rpm, and for this test option, no system warm-up or equivalent procedure may be used. Stop the timer. This shall be done in accordance with SAE J1989. Such equipment extracts and recycles refrigerant or extracts refrigerant for recycling on-site or reclamation off-site. 3 things required for refillable cylinders? has its own means of drawing refrigerant out of appliance. A Porapak Q column at 130 C (266 F) and a hot wire detector are to be used for the analysis. 2.1.4UL PublicationsAvailable from Underwriters Laboratories, 333 Pfingsten Road, Northbrook, IL 60062-2096. Therefore the use of XH-7 or XH-9 deciccant (drier) is necessary. Stop timer. Available from the Superintendent of Documents, U.S. Government Printing Office, Mail Stop: SSOP, Washington, DC 20402-9320. in a res. 8.8.3A weighed sample of 175 to 225 g of liquid HFC-134a is allowed to evaporate at room temperature. The purpose of this document is to provide equipment specifications for CFC-12 (R-12) recycling equipment. 8.2.2The equipment must be preconditioned by processing 13.6 kg of the standard contaminated HFC-134a (see section 8.2.2a) at an ambient of 21 C before starting the test cycle. Refrigerant dissolves in lubricant and, as a result, increases the volume of the recovered lubricant sample. 6.7.2Refrigerant dissolved in this lubricant must be accounted for to prevent lubricant overcharge of the mobile A/C system. 3.4Equipment CertificationThe equipment must be certified by Underwriters Laboratories or an equivalent certifying laboratory to meet this standard. recover 80% of refrig. (b) Effective November 15, 1992, no person may sell or distribute, or offer for sale or distribution, any class I or class II substance that is suitable for use as a refrigerant in motor vehicle air-conditioner and that is in a container which contains less than 20 pounds of such refrigerant to any person unless that person is properly trained and certified under 82.40 or intended the containers for resale only, and so certifies to the seller under 82.42(b)(3). The Chlorine atom can destroy as many as 100,000 ozone molecules. What must a recover device made after nov. 15 1993 be capable of if compressor in system isnt working? 3.2Operate the recovery equipment as covered by the equipment manufacturers recommended procedure. 7.4.1During operation, the equipment must provide overfill protection to assure that during filling or transfer, the tank or storage container cannot exceed 80% of volume at 21.1 C of its maximum rating as defined by DOT standards, 49 CFR 173.304 and American Society of Mechanical Engineers. A sample of vaporized refrigerant liquid shall be separated and analyzed by gas chromatography. (a) The purpose of the regulations in this subpart B is to implement section 609 of the Clean Air Act, as amended (Act) regarding the servicing of motor vehicle air conditioners (MVACs), and to implement section 608 of the Act regarding certain servicing, maintenance, repair and disposal of air conditioners in MVACs and MVAC-like appliances (as that term is defined in 40 CFR 82.152). 8.1The equipment shall be able to clean the contaminated refrigerant in 8.3 to the purity level defined in SAE J2099. 8.1.4The high oil contaminated sample shall consist of CFC-12 with 200,000 ppm (by weight) mineral oil 525 suspension viscosity nominal. (vi) For equipment that recovers and recycles HFC-134a and CFC-12 refrigerant using common circuitry, it was initially purchased before March 6, 1996. can operate at press. 6.2.2Standard contaminated CFC-12 refrigerant, 13.6 Kg sample size, shall consist of liquid CFC-12 with 100 ppm (by weight) moisture at 21 C and 45,000 ppm (by weight) mineral oil 525 suspension nominal and 770 ppm (by weight) of noncondensable gases (air). -and non-condesable gases to the levels set by the Society of Automotive Engineers, To process refrigerant to a level EQUAL to NEW product specification as determined by chemical analysis, -must meet standards of ARI 700-93 (Air conditioning and Refrigeration institute 6.2Any container of recycled refrigerant that has been stored or transferred must be checked prior to use as defined in section 5. 8.2.2bThe HFC-134a compatible lubricant referred to in section 8.2.2a shall be a polyalkylene glycol based synthetic lubricant or equivalent, which shall contain no more than 1000 ppm by weight of moisture. 10.3.3 A weighed sample of 175 to 225 g of liquid refrigerant/lubricant is allowed to evaporate at room temperature. -place a refrigerant label on each cylinder. To reduce chance of over pressuraization/heating/explosion of recovery cylinders it cannot be filled -above 80% of its capacity by weight 4.3.3Transfer of Recycled RefrigerantRecycled refrigerant for recharging and transfer shall be taken from the liquid phase only. 6.7.1The purpose of indicating the amount of lubricant removed is to ensure that a proper amount of new lubricant is returned to the mobile A/C system for compressor lubrication, if the system is to be charged with equipment meeting SAE J2788. 8.2.4The HFC-134a is to be cleaned to the purity level, as defined in SAE J2099. 7.4.1.1The cylinder valve shall comply with the standard for cylinder valves, UL 1769. Aside from the absence of engine operation and the limitations posed by the standard and the use of the electric motor, the test shall otherwise be the same as the test on the Suburban, including test temperature. (4) Effective January 1, 2008, equipment that recovers and recycles HFC-134a refrigerant and equipment that recovers and recycles HFC-134a refrigerant and recharges systems with HFC-134a refrigerant must meet the standards set forth in Appendix C of this subpart based upon J2788HFC-134a (R-134a) Recovery/Recycling Equipment and Recovery/Recycling/Recharging for Mobile Air-Conditioning Systems. ac system LOW press GAS is found b/t what? 10.4.2 This test shall be conducted on liquid phase samples of recycled refrigerant taken from a full container as defined in 7.4 within 30 minutes following the proper venting of noncondensable gases. As in SAE J2788, Section 10.5, as an alternative to a 2005-2007 Chevrolet Suburban with rear A/C (1.4 kg-3.0 lb) system, a laboratory test fixture may be used to certify to SAE J2810 the fixture must be composed entirely of all the original equipment parts of a single model year for the 1.4 kg (3.0 lb) capacity system. -use Nitrogen to pressurize the system -pin-point leaks with soap & water solution. 4.3.1Electrical interlock devices used to prevent cross contamination of refrigerant shall be operated for 100,000 cycles and there shall be no failure that would permit cross contamination of refrigerant. 7.3.1The cylinder valve shall comply with the standard for cylinder valves, UL 1769. If approval is denied under this section, the Administrator shall give written notice to the program setting forth the basis for his determination. e. Weigh the tank on a scale accurate to plus/minus 3 grams. If additional recovery is required after the initial recovery procedure. SAE J1990 establishes equipment specifications for on-site recovery and reuse of CFCs in mobile air-conditioning systems. 7.4.1Additional Storage Tank Requirements. HG of vacuum. Any hoses or lines connected to refrigerant containers on or in the machine also shall have shutoff devices at the connection points, so that the containers may be changed without loss of refrigerant. This shall be determined during SAE J2099 testing.). The sample method fixture defined in Figure 1 of appendix A shall be operated at 24 C. Weigh the tank at the start of the test, on a scale accurate to plus/minus 3 grams, to ensure it contains sufficient refrigerant. hUYH+/e =(vV|0RV aD(TDR% e'9bX4&98sI8%NSd i/Q?m.c;E C l`8>jjVaKGZrMb/x?uHAqahuU-Z|:tEL!$pU{tyB|olQA%179+uAIqV'J0 zuGC-6q/@F.6lef]GN= =E&s[mlq7]Abr]T^/K\e.po izQMY;; Your email address is only used to allow you to reset your password. Therefore, 12 months following the publication date of this standard, it supersedes SAE J1732. Establishing extraction equipment specifications for CFC-12 will provide service facilities with equipment to assure that venting of refrigerant will not occur. 6.3.1The container color must be gray with yellow top to identify that it contains used CFC-12 refrigerant. The exit area is 51.2 cm, and mass flow is 0.825 kg/s. May not be returned to a motor vehicle air conditioning system without first being recyceled or reclaimed. 7.6Service hoses must have shutoff devices located within 30 cm (12 in) of the connection point to the system being serviced to minimize introduction of noncondensable gases into the recovery equipment and the release of the refrigerant when being disconnected. Repeat the operation until the vehicle AC system vacuum level remains stable for 2 min. The vehicle system's service valve cores must remain in the fittings for this procedure. The refrigerant from this equipment must be processed to ARI 700-93 specifications before reuse in a mobile air-conditioning system. The minimum letter size shall be bold type 3mm in height. If desired, this test procedure may be preceded by engine/system operation for up to 15 minutes, up to 2000 rpm. (g) Service for consideration means being paid to perform service, whether it is in cash, credit, goods, or services. Refrigerant may be recycled off-site only if the refrigerant is extracted using recover only equipment, and is subsequently recycled off-site by equipment owned by the person that owns both the recover only equipment and owns or operates the establishment at which the refrigerant was extracted. Completed tests must be graded by an entity or individual who receives no benefit based on the outcome of testing; a fee may be charged for grading. (d) If at any time an approved independent standards testing organization is found to be conducting certification tests for the purposes of this subpart in a manner not consistent with the representations made in its application for approval under this section, the Administrator reserves the right to revoke approval. Where is the purge compress. Establishing such specifications will ensure that system operation with recycled HFC-134a will provide the same level of performance and durability as new refrigerant. -above 80% of its capacity by weight &-the filling level be controlled by mechanical float devices, shut off or weight. 8.4.1The equipment must be preconditioned by processing 13.6 kg (30 lb) of the standard contaminated HFC-134a at an ambient of 21 to 24 C (70 to 75 F) before starting the test cycle. Contaminated refrigerant samples shall be processed at ambient temperatures of 10 and 49 C, without equipment shutting due to any safety devices employed in this equipment. No parts may be added and/or relocated from the OE position in the 2005-07 Suburban. 3.2The equipment shall be suitable for use in an automotive service garage environment and be capable of continuous operation in ambients from 10 C to 49 C (50 F to 120 F). recover 90% of ref. What refrigerant is in 93 and older vehicles? 7.3.2The pressure relief device shall comply with the Pressure Relief Device Standard Part 1Cylinders for Compressed Gases, CGA Pamphlet S-1.1. The filter/drier may be replaced only as noted by section 4.6.2. 3.2 The equipment shall be suitable for use in an automotive service garage environment as defined in section 6.8. The Administrator may approve a program which meets all of the standards in paragraph (a) of this section except test administration if the program, when viewed as a whole, is at least as effective as a program that does meet all the standards. SAE J1739Potential Failure Mode and Effects Analysis in Design (Design FMEA) and Potential Failure Mode and Effects Analysis in Manufacturing and Assembly Processes (Process FMEA) and Effects Analysis for Machinery (Machinery FMEA). 8.10.2This test shall be conducted on recycled refrigerant (taken from the liquid phase) within 30 minutes after the proper venting of noncondensable. The equipment must include a provision for checking the accuracy, per the requirements of 9.1. Test Procedure B at 10 C to 13 C (50 F to 55 F). The marking shall be in letters at least 6 mm (0.25 in) high. Warnings shall be displayed on screens and (printed on printouts where applicable). 10.3.1The amount of lubricant in the recycled sample of refrigerant/lubricant is to be determined by gravimetric analysis. 8.2.2aThe standard contaminated refrigerant shall consist of liquid HFC-134a with 1300 ppm (by weight) moisture (equivalent to saturation at 38[100 F]), 45,000 ppm (by weight) HFC-134a compatible lubricant, and 1000 ppm (by weight) of noncondensable gases (air). Why must you never pressurize a system with oxygen or compressed air? The difference between weight A and weight B should be equal to the recommended charge that was installed per the machine's display, within 15 g (0.5 oz). refrig. Ambient temperature shall be within the range of 21 C to 24 C (70 F to 75 F) for this test, which shall be performed without the immediately prior engine operation permitted by SAE J2788, Section 10.3, Step No.1. -attach cylinder to the recovery unit -reduce the cylinder to a vacuum -mark the cylinder empty. In particular, applications must document: (i) The equipment present at the organization that will be used for equipment testing; (ii) The expertise in equipment testing and the technical experience of the organization's personnel; (iii) Thorough knowledge of the standards as they appear in the applicable appendices of this subpart; and. (1) Any person who owns approved refrigerant recycling equipment certified under 82.36(a)(2) must maintain records of the name and address of any facility to which refrigerant is sent. The sample method fixture, defined in Fig. 6.4.1The cylinder valve shall comply with the standard for cylinder valves, UL 1769. After initial recovery procedures, the technician should? 6.2If the marketer permits use of a refillable refrigerant tank, a method must be provided (including any necessary fittings) for transfer to a system that ensures proper handling (recycling or other, environmentally-legal disposal). Air, with 6.4.3The container assembly shall be marked to indicate the first retest date, which shall be 5 years after date of manufacture. 6.2The equipment must prominently display the manufacturer's name, address and any items that require maintenance or replacement that affect the proper operation of the equipment. ~E,hpN-% mZzIo-`*B41pIw K) Q Operation manuals must cover information for complete maintenance of the equipment to assure proper operation. 10.2The machine must have a self-contained provision for checking accuracy of the indicated amount of refrigerant recovered in liquid or vapor or mixture form(s) from a vehicle system and (if applicable) charged into a vehicle, and adjusting if necessary, to meet requirements of 9.1, 9.2. -discarded. Note exception for noncondensable gas determination in 8.9.4. If the difference is greater than 15 g (3 g), the machine fails the charge accuracy test, and no other tests shall be performed at that time. -reduced marine life The minimum letter size shall be bold type 3 mm in height. 7.4All flexible hoses must comply with SAE J2196. 10.1.1The processed contaminated samples shall be analyzed according to the following procedure. defines small appliances as products that are fully manufac.,charged,and hermetically sealed in a factory with _ pounds or less of ref.? If the recovery is completed in no more than the 30.0 minutes, measure the oil level in the reservoir, remove the reservoir and then determine the amount of refrigerant recovered, as detailed in Nos. The latest issue of SAE publications shall apply. Continuous is defined as completing recovery/recycle and recharge (if applicable) operations with no more than a brief reset period between vehicles, and shall not include time delays for allowing a system to outgas (which shall be part of the recovery period provided by this standard). Although it may feel like you're playing a game, your brain is still making more connections with the information to help you out. (d) Recertification. the last 12" of freon left over in lines from shut off valve. repeat the recovery process untile the A/C system vacuum remains stable for 2 min. SAE J2196Service Hoses for Automotive Air-Conditioning (fittings modified). 2.1 Applicable DocumentsThe following publications form a part of this specification to the extent specified. This information applies to equipment used to service automobiles, light trucks, and other vehicles with similar CFC-12 air-conditioning systems. These specifications are for equipment that recover, but does not recycle, any single, specific automotive refrigerant other than CFC-12 or HFC-134a, including a blend refrigerant. Applicable DocumentsThe following documents form a part of this specification to the extent specified herein. -date stamped every 5 years. When disposing of empty/near empty cylinders..? -wear safety glasses -wear proective gloves -follow all safety precautions for the equpment. (B) Subsequently recycled by the facility that charges or recharges the refrigerant into an MVAC or MVAC-like appliance, properly using approved refrigerant recycling equipment in accordance with any applicable recommended service procedures set forth in the appendices to this subpart B. 8.6.1The R-12 is to be cleaned to the minimum purity level, as defined in SAE J1991, with the equipment operating in a stable ambient of 10, 21, and 49 C (50, 70, and 120 F) and processing the samples as defined in 8.5. One chlorine atome in the stratospher can destroy up to how many ozone molecules? Stop the timer. Removed lubricant from the system and/or the equipment shall be disposed on in accordance with the applicable federal, state, and local procedures and regulations.